GEMC-BM/PS WIRING DIAGRAM
T1
T2
T3
T9
T8
T7
T6
T4
T5
+
T11
T10
T13
T12
BELL AUX PWR PGM1 BURG BUS AUX RELAY PGM2
+ – +
GRN YEL COM N/C N/O
+12V
Notes:
1. All outputs are power limited.
2. All Burglary / Access circuits are isolated from Fire circuits.
3. Wire range 14-22 AWG.
E2
(Not
used)
BATTERY
Black
(–)
E1
Red
(+)
BURG
SERV
JP2
ON OFF
(LED)
J2
JP1
MB
PWR
OFF
MB
PWR
ON
AUX RELAY
Terminal 11: COM
Terminal 12: N/C
Terminal 13: N/O
JP1 (Motherboard Power On/Off Jumper)
This three-pin jumper allows one of two options:
MB PWR ON: Place the shunt on the two right pins for power
to be provided to the GEMC-BM/PS (and its connected de-
vices) from both the motherboard and the battery. The
jumper is placed on these two right pins ("MB PWR ON") at
the factory.
MB PWR OFF: Place the shunt on the two left pins (or re-
move the shunt entirely) to remove power from the mother-
board, thus allowing the GEMC-BM/PS (and its connected
devices) to be powered by the battery only. To remove all
power, remove the flying battery leads from the battery termi-
nals.
JP2 (Burg Service Jumper)
For Combination Fire and Burglary systems. When the shunt
is placed on the two left pins ("ON") of this three-pin jumper,
the system enters a special mode named "Burg Service
Mode" where the system stops processing Burglary (non-Fire)
alarm functions to permit the Burglary part of the system to be
serviced (changed) while allowing the Fire system to continue
to function as intended. When servicing the Burglary system,
we recommend entering Burg Service Mode before removing
power to avoid the various troubles (such as a trouble E12
"Burg EZM Fail to Respond") that will occur. When Burg Ser-
vice Mode is on, an LED located just below the jumper will
light. A Burg Service Mode jumper is also located on the con-
trol panel motherboard that is in parallel with the JP2 jumper
on the GEMC-BM/PS; either jumper can be used to initiate
Burg Service Mode, and the LED located just below the
jumper will light.
J2 (Motherboard Socket Connector)
12 pin data connector to allow a data connection between the
motherboard and the GEMC-BM/PS Burglary module.
REMOVE JUMPER "R" FOR
DRY CONTACTS
(JUMPER INSTALLED AT
FACTORY)
R
WARNING: INCORRECT CONNECTION MAY RESULT IN
IMPROPER OPERATION OR DAMAGE TO THE SYSTEM.